Univeritetet for miljø- og biovitenskap, IMT-instituttet
Lab: Industrial PID controller (Fuji PYX5) for speed
control
What the lab is about
In this part of the course you will get experience in using an industrial PID-controller,
the Fuji PYX5 (price approximately NOK 3300). The controller will be used to
control the rotational speed of a DC-motor.
Equipment
Tasks
- Get to know the controller by browsing the
instruction manual
together with the teacher.
- Do the following tasks on your own (in student groups):
- Set the controller parameters as indicated below, cf. Appendix 5:
Parameter List in the manual (not all parameters in Appendix 5 are
available in the present controller). Find from the manual the meaning of
each of the parameters. The parameters in the list below is in same order as
they appear in the controller.
- LOCK = 3
- OUT1: No setting required.
- MOD = Man (= Manual)
- AT = OFF
- P = 100
- I = 0
- D = 0
- AR = 100 (dont care about the meaning of this parameter)
- MAN = 0
- AL1T = 0001
- AL11 = 90
- A11H = 1
- AL2T = 0002
- AL21 = 10
- A21H = 1
- Loop = 0 (dont care about the meaning of this parameter)
- PVT = 4111
- PVF = 100
- PVB = 0
- PVD = 0
- TF = 4.0
- SFT = 0
- SVH = 100
- SVL = 0
- CTRL = PID
- DT = 0.5 (the effective value of this parameter is 0.5 no matter the
value set)
- REV1 = REV
- TC-1 = 2 (this parameter is however not active)
- MV-H = 100
- MV-L = 0
- BURN = 1 (don't care about the meaning of this parameter)
- Connect the controller to the process as follows:
- Controller input terminal no. 16 to Tachometer minus (not plus)
- Controller input terminal no. 18 to Tachometer plus (not minus)
- Controller output terminal no. 13 to Servo amplifier input
("Styrespenning") plus
- Controller output terminal no. 14 to Servo amplifier input
("Styrespenning") minus
Ask the teacher to check the connections.
- With the controller (still) in manual mode (open loop control): Adjust
the manual control signal so that the speed is approximately 50% (you can
adjust the control signal with the controller in Operation Mode). Apply a
small approx. constant load torque to the motor (use your finger). What is
the steady-state control error (in %)?
- Set the controller in automatic mode (closed loop control). Set the setpoint
equal to 50%.
- Execute auto-tuning. What are the resulting P-, I- and D-values? What is
the value of the controller gain (Kp) that corresponds to the P-value from
the auto-tuning?
- Is the stability of the control system ok? (Excite with a step in the
setpoint.)
- Set setpoint to 50%. Apply a small approximately constant load torque to the
motor (use your finger). What is the steady-state control error (in %)?
- What happens to the stability of the control system if the controller
mode is
changed from reverse action to direct action (denoted both direct and normal
in the manual)?
[Fagets hjemmeside] [Fagets framdriftsplan]
Oppdatert 26.02.05 av Finn
Haugen, faglærer (e-postadresse: finn@techteach.no).
|