Lab: Industrial PID controller (Fuji PYX5) for speed 
    control
    What the lab is about
    In this part of the course you will get experience in using an industrial PID-controller, 
    the Fuji PYX5 (price approximately NOK 3300). The controller will be used to 
    control the rotational speed of a DC-motor. 
    Equipment
    
    Practical information
    The teacher will describe the construction and function of the equipment. 
    The lab takes about 1 hour. You will be working in groups (there are 4 
    copies of the equipment). 
    Tasks
    
      - Get to know the controller by browsing the
      instruction manual 
      together with the teacher.
 
  - Do the following tasks on your own (in student groups):
    - Set the controller parameters as indicated below, cf. Appendix 5: 
    Parameter List in the manual (not all parameters in Appendix 5 are 
    available in the present controller). Find from the manual the meaning of 
    each of the parameters. The parameters in the list below is in same order as 
    they appear in the controller.
      - LOCK = 3
 
      - OUT1: No setting required.
 
      - MOD = Man (= Manual)
 
      - AT = OFF
 
      - P = 100
 
      - I = 0
 
      - D = 0
 
      - AR = 100 (dont care about the meaning of this parameter)
 
      - MAN = 0
 
      - AL1T = 0001
 
      - AL11 = 90
 
      - A11H = 1
 
      - AL2T = 0002
 
      - AL21 = 10
 
      - A21H = 1
 
      - Loop = 0 (dont care about the meaning of this parameter)
 
      - PVT = 4111
 
      - PVF = 100
 
      - PVB = 0
 
      - PVD = 0
 
      - TF = 4.0
 
      - SFT = 0
 
      - SVH = 100
 
      - SVL = 0
 
      - CTRL = PID
 
      - DT = 0.5 (the effective value of this parameter is 0.5 no matter the 
      value set)
 
      - REV1 = REV
 
      - TC-1 = 2 (this parameter is however not active)
 
      - MV-H = 100
 
      - MV-L = 0
 
      - BURN = 1 (don't care about the meaning of this parameter)
 
     
     
      - Connect the controller to the process as follows:
    - Controller input terminal no. 16 to Tachometer minus (not plus)
 
    - Controller input terminal no. 18 to Tachometer plus (not minus)
 
    - Controller output terminal no. 13 to Servo amplifier input 
    ("Styrespenning") plus
 
    - Controller output terminal no. 14 to Servo amplifier input 
    ("Styrespenning") minus
 
   
      Ask the teacher to check the connections.  
      - With the controller (still) in manual mode (open loop control): Adjust 
      the manual control signal so that the speed is approximately 50% (you can 
      adjust the control signal with the controller in Operation Mode). Apply a 
      small approx. constant load torque to the motor (use your finger). What is 
      the steady-state control error (in %)?
 
    - Set the controller in automatic mode (closed loop control). Set the setpoint 
    equal to 50%.
    - Execute auto-tuning. What are the resulting P-, I- and D-values? What is 
    the value of the controller gain (Kp) that corresponds to the P-value from 
    the auto-tuning?
 
    - Is the stability of the control system ok? (Excite with a step in the 
    setpoint.)
 
    - Set setpoint to 50%. Apply a small approximately constant load torque to the 
    motor (use your finger). What is the steady-state control error (in %)?
 
   
     
    - What happens to the stability of the control system if the controller 
    mode is 
    changed from reverse action to direct action? (In the manual, direct 
    action is denoted direct mode and also normal 
    mode in the manual.)
 
   
   
     
    
 
 [Fagets hjemmeside]  [Fagets framdriftsplan] 
 
Oppdatert 17.9.06 av  Finn
Haugen, faglærer (e-postadresse: finn@techteach.no). 
       |